# Waveform Record (waveform) The waveform record type is used to interface waveform digitizers. The record stores its data in arrays. The array can contain any of the supported data types. ## Parameter Fields The record-specific fields are described below, grouped by functionality. ### Scan Parameters The waveform record has the standard fields for specifying under what circumstances the record will be processed. These fields are listed in [Scan Fields](dbCommonRecord.md#scan-fields). ### Read Parameters These fields are configurable by the user to specify how and from where the record reads its data. How the INP field is configured determines where the waveform gets its input. It can be a hardware address, a channel access or database link, or a constant. Only in records that use soft device support can the INP field be a channel access link, a database link, or a constant. Otherwise, the INP field must be a hardware address. #### Fields related to waveform reading | Field | Summary | Type | DCT | Default | Read | Write | CA PP | | ----- | -------------------------- | ------------- | --- | ------- | ---- | ----- | ----- | | DTYP | Device Type | DEVICE | Yes | | Yes | Yes | No | | INP | Input Specification | INLINK | Yes | | Yes | Yes | No | | NELM | Number of Elements | ULONG | Yes | 1 | Yes | No | No | | FTVL | Field Type of Value | MENU [menuFtype](menuFtype.md) | Yes | | Yes | No | No | | RARM | Rearm the waveform | SHORT | Yes | | Yes | Yes | Yes | The DTYP field must contain the name of the appropriate device support module. The values retrieved from the input link are placed in an array referenced by VAL. (If the INP link is a constant, elements can be placed in the array via dbPuts.) NELM specifies the number of elements that the array will hold, while FTVL specifies the data type of the elements (follow the link in the table above for a list of the available choices). The RARM field used to cause some device types to re-arm when it was set to 1, but we don't know of any such devices any more. ### Operator Display Parameters These parameters are used to present meaningful data to the operator. They display the value and other parameters of the waveform either textually or graphically. #### Fields related to _Operator Display_ | Field | Summary | Type | DCT | Default | Read | Write | CA PP | | ----- | -------------------------- | ------------- | --- | ------- | ---- | ----- | ----- | | EGU | Engineering Units | STRING \[16\] | Yes | | Yes | Yes | No | | HOPR | High Operating Range | DOUBLE | Yes | | Yes | Yes | No | | LOPR | Low Operating Range | DOUBLE | Yes | | Yes | Yes | No | | PREC | Display Precision | SHORT | Yes | | Yes | Yes | No | | NAME | Record Name | STRING \[61\] | No | | Yes | No | No | | DESC | Descriptor | STRING \[41\] | Yes | | Yes | Yes | No | EGU is a string of up to 16 characters describing the units that the waveform measures. It is retrieved by the `get_units` record support routine. The HOPR and LOPR fields set the upper and lower display limits for array elements referenced by the VAL field. Both the `get_graphic_double` and `get_control_double` record support routines retrieve these fields. The PREC field determines the floating point precision with which to display the array values. It is used whenever the `get_precision` record support routine is called. See [Fields Common to All Record Types](dbCommonRecord.md#operator-display-parameters) for more on the record name (NAME) and description (DESC) fields. ### Alarm Parameters The waveform record has the alarm parameters common to all record types. [Alarm Fields](dbCommonRecord.md#alarm-fields) lists the fields related to alarms that are common to all record types. ### Monitor Parameters These parameters are used to determine when to send monitors placed on the VAL field. The APST and MPST fields are a menu with choices `Always` and `On Change`. The default is `Always`, thus monitors will normally be sent every time the record processes. Selecting `On Change` causes a 32-bit hash of the VAL field buffer to be calculated and compared with the previous hash value every time the record processes; the monitor will only be sent if the hash is different, indicating that the buffer has changed. Note that there is a small chance that two different value buffers might result in the same hash value, so for critical systems `Always` may be a better choice, even though it re-sends duplicate data. | Field | Summary | Type | DCT | Default | Read | Write | CA PP | | ----- | -------------------------- | ------------- | --- | ------- | ---- | ----- | ----- | | APST | Post Archive Monitors | MENU [waveformPOST](#menu-waveformpost) | Yes | | Yes | Yes | No | | MPST | Post Value Monitors | MENU [waveformPOST](#menu-waveformpost) | Yes | | Yes | Yes | No | | HASH | Hash of OnChange data. | ULONG | No | | Yes | Yes | No | #### Menu waveformPOST This menu defines the possible choices for `APST` and `MPST` fields: | Index | Identifier | Choice String | | ----- | -------------------------------------- | ---------------------- | | 0 | waveformPOST\_Always | Always | | 1 | waveformPOST\_OnChange | On Change | ### Run-time Parameters These parameters are used by the run-time code for processing the waveform. They are not configured using a configuration tool. Only the VAL field is modifiable at run-time. VAL references the array where the waveform stores its data. The BPTR field holds the address of the array. The NORD field indicates the number of elements that were read into the array. The BUSY field permits asynchronous device support to collect array elements sequentially in multiple read cycles which may call the record's `process()` method many times before completing a read operation. Such a device would set BUSY to TRUE along with setting PACT at the start of acquisition (it could also set NORD to 0 and use it to keep track of how many elements have been received). After receiving the last element the `read_wf()` routine would clear BUSY which informs the record's `process()` method that the read has finished. Note that CA clients that perform gets of the VAL field can see partially filled arrays when this type of device support is used, so the BUSY field is almost never used today. | Field | Summary | Type | DCT | Default | Read | Write | CA PP | | ----- | -------------------------- | ------------- | --- | ------- | ---- | ----- | ----- | | VAL | Value | Set by FTVL\[NELM\] | No | | Yes | Yes | Yes | | BPTR | Buffer Pointer | NOACCESS | No | | No | No | No | | NORD | Number elements read | ULONG | No | | Yes | No | No | | BUSY | Busy Indicator | SHORT | No | | Yes | No | No | ### Simulation Mode Parameters The following fields are used to operate the record in simulation mode. If SIMM (fetched through SIML) is YES, the record is put in SIMS severity and the value is fetched through SIOL. SSCN sets a different SCAN mechanism to use in simulation mode. SDLY sets a delay (in sec) that is used for asynchronous simulation processing. See [Input Simulation Fields](dbCommonInput.md#input-simulation-fields) for more information on simulation mode and its fields. | Field | Summary | Type | DCT | Default | Read | Write | CA PP | | ----- | -------------------------- | ------------- | --- | ------- | ---- | ----- | ----- | | SIML | Simulation Mode Link | INLINK | Yes | | Yes | Yes | No | | SIMM | Simulation Mode | MENU [menuYesNo](menuYesNo.md) | No | | Yes | Yes | No | | SIOL | Simulation Input Link | INLINK | Yes | | Yes | Yes | No | | SIMS | Simulation Mode Severity | MENU [menuAlarmSevr](menuAlarmSevr.md) | Yes | | Yes | Yes | No | | SDLY | Sim. Mode Async Delay | DOUBLE | Yes | -1.0 | Yes | Yes | No | | SSCN | Sim. Mode Scan | MENU [menuScan](menuScan.md) | Yes | 65535 | Yes | Yes | No |